Fluke 1507 Insulation Resistance Tester
Fluke 1507 is a versatile, compact, handheld insulation tester for advanced industrial and electrical insulation testing. Its multiple test voltages make it the ideal tool for many troubleshooting, commissioning, and preventative maintenance applications. Take advantage of the 1507 full feature set to easily and quickly perform advanced insulation resistance testing. Its handy size and light weight make it easy to pack and use. Additional features, like the remote probe, save both time and money, especially when performing repetitive tests. And its reasonable price and rugged reliability make it an excellent value.
Features:
- Rugged, compact advanced insulation resistance tester for electrical contractors and industrial and commercial electricians
- Performs insulation tests from 0.01 M? to 2.0 G?
- Includes live circuit detection to prevent insulation test if voltage >30 volt is detected
- Includes auto-discharge of capacitive voltage for added user protection
- Provides lo-ohms earth-bond continuity
- Simplifies repetitive or hard-to-reach testing with the remote test probe
- Saves battery power with auto power off
- Presents results on a large, backlit display
- Features CAT IV 600 V overvoltage category rating
- Accepts optional Fluke TPAK magnetic hanging system to free your hands for other work
- Automatically calculates Polarization Index and Dielectric Absorption Ratio
Specifications:
Battery Type |
AA |
Maximum Voltage Applied To Any Terminal: |
600 volt AC-RMS or DC |
Storage Temperature |
-40 to 60 degree Celsius |
Operating Temperature |
-20 to 55 degree Celsius |
Temperature Co-efficient |
0.05 x (Specified Accuracy) per degree Celsius for temperatures < 18 degree Celsius or > 28 degree Celsius |
Relative Humidity |
0 to 95 percent at 10 to 30 degree Celsius |
0 to 75 percent at 30 to 40 degree Celsius |
0 to 40 percent at 40 to 55 degree Celsius |
Vibration |
Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument |
Shock |
1 meter drop per IEC 61010-1 2nd Edition (1 meter drop test, six sides, oak floor) |
Measurement Range |
0.01 to 2000 MΩ |
Test Voltage |
500 volt, 1000 volt |
Test Voltage Accuracy |
+ 20 percent,-0 percent |
Short Circuit Current |
1 mA nominal |
Auto Discharge |
Discharge time < 0.5 second for C = 1 µF or less |
Live Circuit Indicator |
Inhibit test if terminal voltage > 30 volt prior to initialization of test |
Maximum Capacitive Load |
Operable with up to 1 µF load |
Measure Accuracy |
50 volt |
±(3 percent + 5) |
100 volt |
±(3 percent + 5) |
250 volt |
±(1.5 percent + 5) |
500 volt |
±(1.5 percent + 5) |
1000 volt |
±(1.5 percent + 5) to 2000 MΩ, ±(10% + 3) above 2000 MΩ |
AC/DC Voltage Measurement |
Accuracy |
Range |
600 volt |
Resolution |
0.1 volt |
50 Hz to 400 Hz ±(percent of Rdg + Digits) |
±(2 percent + 3) |
Input Impedance |
3 MΩ (nominal), < 100 pF |
Common Mode Rejection Ratio (1 kΩ unbalanced) |
> 60 dB at DC, 50 or 60 Hz |
Overload Protection |
600 volt-Rms or DC |
Earth Bond Resistance Measurement |
Range/Resolution |
20.00 Ω |
0.01 Ω |
200.0 Ω |
0.1 Ω |
2000 Ω |
1.0 Ω |
20.00 kΩ |
0.01 kΩ |
Accuracy |
±(1.5% + 3) |
Overload Protection |
2 volt RMS or DC |
Open Circuit Test Voltage |
> 4.0 volt, < 8 volt |
Short Circuit Current |
> 200.0 mA |
Size |
50 x 100 x 203 cm |
Weight |
0.55 kg |
Includes:
- Remote Probe
- Test Leads
- Test Probes
- Alligator Clips
- User Documentation